Main technical performance and parameters
1 BWY - 80 3 A ( TH ) technical parameters
1.1 Working conditions: ambient temperature ( -40 ~ +55 ) ℃ , relative humidity ≤ 95% .
1.2 Measuring range : ( 0 ~ 100 ) ℃ .
1.3 Accuracy: Class 1.5 (the maximum allowable error of detection point is ± 1.5 ℃ ) .
1.4 Switching action error: ± 2 ℃ .
1.5 Switching difference: ( 6±2 ) ℃ .
1.6 Switch rated power: AC220V / 3 A
1.7 Protection class: IP55 .
1.8 Temperature bulb size: Φ14 , the temperature bulb insertion depth is not less than 150mm; the installation thread is ( M27×2 ) mm or ( M33 × 2 ) mm .
1.9 Capillary length : 5 m .
2.1 BWY - 80 2A ( TH ) technical parameters
2.1 Output signal: Pt100 platinum resistance signal
2.2 Working conditions: ambient temperature ( -40 ~ +55 ) ℃ , relative humidity ≤ 95% .
2.3 Measuring range : ( 0 ~ 100 ) ℃
2.4 Accuracy: Class 1.5 ( the maximum allowable error of detection point is ± 1.5 ℃ ) .
2.5 Switching action error : ± 2 ℃ .
2.5 Switching difference: ( 6±2 ) ℃ .
2.6 Switch rated power: AC220V / 3A .
2.7 Protection class: IP55 .
2.8 Temperature bulb size: Φ14 , the insertion depth is not less than 150 mm ; installation thread : ( M27×2 ) mm .
2.9 Capillary length : 5 m (can be customized according to user requirements) .